STUDI EXPERIMENTAL RETROFIT PERFORMANSI AC INVERTER BERBASIS R32 DAN R410A KE R1270

WIRAWAN, Hendar and Fajar TK, Berkah and Utomo, M.S.K. Tony Suryo (2023) STUDI EXPERIMENTAL RETROFIT PERFORMANSI AC INVERTER BERBASIS R32 DAN R410A KE R1270. Masters thesis, UNIVERSITAS DIPONEGORO.

[img] Text
Halaman Cover.pdf

Download (1MB)
[img] Text
BAB I_Pendahuluan.pdf

Download (50kB)
[img] Text
BAB II_Landasan Teori.pdf

Download (513kB)
[img] Text
BAB III_Metodologi Penelitian.pdf
Restricted to Repository staff only

Download (700kB)
[img] Text
BAB IV_Pembahasan.pdf
Restricted to Repository staff only

Download (2MB)
[img] Text
BAB V_Penutup.pdf

Download (138kB)
[img] Text
Lampiran.pdf
Restricted to Repository staff only

Download (1MB)

Abstract

Dengan diberlakukannya kebijakan terkait pelarangan penggunaan R22 sejak tahun 2015 terkait dampak perusakannya pada lapisan ozon (BPO), di pasaran telah beredar AC jenis split yang menggunakan refrigeran R410a dan R32. Di dalam aplikasinya, peralatan AC jenis split yang menggunakan refrigerant R410a yang kemudian diikuti dengan hadirnya R32 dianggap masih terlalu besar dalam mengkonsumsi energi listrik.
Tujuan dari studi experimental ini adalah untuk memberikan gambaran kinerja energi dari perbandingan refrigeran (R32 dan R410a terhadap R1270) sehingga dapat diketahui kemampuan R1270 sebagai refrigeran pengganti R32 dan R410a.
Analisis yang akan dilakukan di dalam penelitian ini adalah dengan mengevaluasi perbandingan kinerja energi mesin pendingin ruangan jenis AC split menggunakan analisis energi dan efisiensi energi menggunakan standar VDMA 24247-2 pada peralatan sistem AC split inverter.
Untuk nilai efisiensi energi total R32 dan R1270 dengan berbagai kondisi berdasarkan standar VDMA 24247-2 secara berturut-turut adalah: 6,38%, 18,15%, 20,37%, dan 21,86%. Sedangkan efisiensi energi total R410a dan R1270 dengan berbagai kondisi adalah 5,14%, 6,25%, 6%, dan 6,84%.
Dari hasil penelitian ini diperoleh gambaran bahwa retrofit refrigerant R32 ke R1270 pada AC inverter kapasitas 1 PK dapat mereduksi pembebanan listrik sebesar 30% dan untuk AC inverter kapasitas 1,5 PK dari R410a ke R1270 dapat mereduksi pembebanan listrik sebesar 40%. Selain itu, kualitas listrik terhadap penggantian R32 dan R410a ke R1270 masih sangat baik (cos phi 0,98-1).
Kata kunci: R32, R410a, R1270, AC inverter, efisiensi, standar VDMA 24247-2

With the enactment of a policy related to the ban on the use of R22 since 2015 due to the impact that damages the ozone layer (BPO), split type air conditioners have been circulating on the market that use R410a and R32 refrigerants. In practice, split-type AC equipment that uses R410a refrigerant, followed by R32, is considered to still consume too much electrical energy.
The purpose of this experimental study is to provide a comparison of the energy performance of refrigerants (R32 and R410a to R1270) so that R1270 can be identified as a replacement refrigerant for R32 and R410a.
The analysis that will be carried out in this study is to evaluate the energy performance comparison of split type AC using energy analysis and energy efficiency using the VDMA 24247-2 standard on split inverter AC system equipment.
The total energy efficiency values of R32 and R1270 under various conditions based on the VDMA 24247-2 standard are: 6.38%, 18.15%, 20.37% and 21.86%, respectively. While the total energy efficiency of R410a and R1270 with various conditions is 5.14%, 6.25%, 6% and 6.84%.
From the results of this study, it was obtained an illustration that retrofit refrigerant R32 to R1270 in an inverter AC with a capacity of 1 PK can reduce the electricity load by 30% and for an inverter AC with a capacity of 1.5 PK from R410a to R1270 this can reduce the electricity load by up to 40%. In addition, the quality of electricity for the replacement of R32 and R410a to R1270 is still very good (cos phi 0.98-1).
Keywords: R32, R410a, R1270, AC inverter, efficiency, VDMA 24247-2 standard

Item Type: Thesis (Masters)
Uncontrolled Keywords: R32, R410a, R1270, AC inverter, efisiensi, standar VDMA 24247-2
Subjects: Engineering
Divisions: Postgraduate Program > Master Program in Energy
Depositing User: ekana listianawati
Date Deposited: 14 Sep 2023 02:52
Last Modified: 14 Sep 2023 02:52
URI: https://eprints2.undip.ac.id/id/eprint/16252