Kiono, Berkah Fajar T Berkah Fajar C1 - Unsteady exergy. International Journal of Refrigeration.
PDF (Berkah Fakar C1 -Unsteady exergy)
Unsteady exergy analysis for a recycle and recovery machine.pdf Download (1MB) |
Abstract
Machine 2R is necessary in order to avoid the release of refrigerant during the repair of an air conditioning machine. The main goals of this paper are to determine the rate of exergy transfer, the rate of exergy destruction and the rate of exergy change in the compressor, condenser, oil separator and 2R machine. This study also determines the performance of the 2R machine. Pressure, temperature and mass of the refrigerant were measured every 0.5 minutes for 10 minutes. In conclusion, the results of this analysis show that the rate of
destruction exergy in the compressor is 59.98%, and 25.37% in the condenser. The value of the Residual Trapped Refrigerant (RTR) of recycling and recovery machine meets the AHRI standard, that is, 34 grams, and the value of the Refrigerant Loss (RL) complies with the
AHRI standard, which is 10 grams, while its performance is 91.2%.